AED. 138.00
The Sparta SPTASD1-A1 is a star delta timer relay used in motor starter panels to run a motor in star connection first, then switch it to delta once it has...
Availability: 40 In Stock
Sku: SPTASD1-A1
Product Type: Star Delta Timer
Vendor: Sparta

The Sparta SPTASD1-A1 is a star delta timer relay used in motor starter panels to run a motor in star connection first, then switch it to delta once it has picked up speed. Starting in star keeps inrush current down, which protects the supply and the motor windings on larger loads where a direct on line start would be too harsh.

The relay handles both parts of that sequence. T1 sets how long the motor stays in star and is adjustable from 0.1 seconds up to 10 minutes, so you can match it to the load and run up time. T2 is the changeover gap, adjustable between 0.1 and 1 second, which keeps the star contactor fully open before the delta contactor closes. Without that gap the two contactors can overlap and short the supply.

Supply is the useful part of this model. It accepts anything from 24 to 240V AC or DC, so the same unit fits panels running on a 24V control supply and panels fed straight from a 230V line. That one wide range saves holding two separate part numbers in stock.

It clips onto standard 35mm din rail and sits alongside the contactors and overload relay in the starter panel. At 113 grams it adds almost nothing to the rail, and the IP20 body is built for use inside an enclosure.

Key Features

  • Controls both star run time and delta changeover from one unit

  • T1 adjustable from 0.1 seconds to 10 minutes for the star stage

  • T2 changeover gap adjustable from 0.1 to 1 second

  • Wide 24 to 240V AC or DC supply suits most panel control voltages

  • Output contacts rated 10 or 16A on resistive load

  • Basic error under 1 percent and repeat error under 0.5 percent

  • Snap fit 35mm din rail mounting

  • Compact 113 gram body saves rail space

Technical Specifications

Specification

Detail

Product Type

Star Delta Time Relay

Time Range

T1: 0.1S – 10 Min (Adjustable) & T2: 0.1S – 1S

Operating Voltage

AC/DC 24-240V

Frequency

50-60Hz

Delay Accuracy

Basic error <1%, Mechanical error <10%, Repeat error <0.5%, Voltage jump error <1%

Mechanical life

1Ɨ10^5 (Resistive load, room temperature, 1s on & 9s off)

Output Contact Capacity

AC/DC24-240V Power supply 10/16A(AC1-Resistive)

Environment

Working temperature: -10-55ā„ƒ Relative humidity: ≤85% Altitude: ≤2000 meters Storage temperature: -20-75ā„ƒ, no rain, snow, salt fog and corrosive

Protection Degree

IP20

Installation Method

35mm Din Rail type

Weight

113 grams

Model

SPTASD1-A1

Make

Sparta

Origin

China

Common Applications

Star delta starter panels for pumps, fans and compressors, HVAC plant rooms, water treatment and irrigation pump sets, conveyor and crusher drives, workshop machinery with large induction motors, generator and borehole panels, and any three phase motor above the size where a direct on line start causes voltage dip.

Related Star Delta Timers

Supply voltage is the first thing to match. If the panel control supply sits above 240V, the SPTASD1-A2 star delta timer relay is the same Sparta unit with a 100 to 380V range, which suits panels fed directly from line voltage.

Where the panel uses plug in relay bases instead of din rail, the ARD star delta timer from Anly is an 8 pin 220VAC model made in Taiwan.

For the complete range see the star delta timer collection, or the parent digital and analog timers category which also covers multi range, twin and countdown timers.

A star delta timer is one part of the starter. The rest of the panel usually needs magnetic contactors for the three switching stages, a thermal overload relay for motor protection, and an MCB on the incomer. For manual star delta changeover without a timer, see the motor reversing and star delta switch range.

Why Buy From Qahraba

Qahraba supplies electrical contractors, panel builders and procurement engineers across the UAE and worldwide. Local UAE orders ship within 1 to 2 working days, or collect free from our Dubai store. Call or WhatsApp +971 52 913 9543 for bulk pricing or wiring support.


FAQ,s

What does a star delta timer do?

It controls the two stage start of a three phase motor. The motor runs in star connection for a set time to limit inrush current, then the timer switches it over to delta for normal running.

What is the difference between T1 and T2?

T1 is how long the motor stays in star, adjustable from 0.1 seconds to 10 minutes. T2 is the short gap between the star contactor opening and the delta contactor closing, adjustable from 0.1 to 1 second.

Why is the T2 changeover delay needed?

It stops both contactors being closed at the same time. Without that gap the star and delta contactors can overlap, which shorts the supply and damages the contactors.

What control voltage does the SPTASD1-A1 take?

Anything from 24 to 240V, AC or DC. For panels running above that, choose the 100 to 380V version instead.

How do I set the star time?

Set T1 long enough for the motor to reach roughly 80 percent of running speed under its actual load. Too short and the motor pulls high current on changeover, too long and it wastes torque in star.

Does it mount on standard din rail?

Yes, it clips onto 35mm din rail alongside the contactors and overload relay in the starter panel.

Ā 

Shipping:


Can I track my order?

Once we ship the items we will send you an email containing the shipping company name and tracking number for your reference. You can always contact them for accurate shipping time.

How many days will delivery take?

All local UAE deliveries will be done within 1-2 working days from time of confirmation.

What are shipping costs?

All local UAE deliveries cost a flat fee of AED 25 for order values below AED 250. All orders above this value will be shipped for free.

Do you ship internationally?

Yes we ship globally. You can choose your point of destination at checkout. Shipping costs will also be displayed at checkout.

Orders:


Can I amend my order?

If you wish to cancel your order, log in to your account and file for a return. You can always call and request changes as well if you prefer to do so. Refer to our returns and refunds page to know more about this policy.

Order items are out of stock

If you have placed an order for an item which is no longer in stock, we will process your refund immediately. We are sorry for the inconvenience caused

Order Validity:

Cash on Delivery/Collection orders placed on our website will be considered as cancelled if the order is not collected within 7 days from confirmation.

Customer Account


Why should I create an account?

Creating an account ensures that all your details are saved ensuring a quick checkout. In addition you can always review all your previous orders with us.

Tax Invoices

Send us an email at orders@qahraba.com with your order number requesting for a tax invoice and our team will send it as soon as possible.

Refund policy


If would like to return an order, kindly log in to your account and request a refund. You can refer to our returns and refunds policy page

Note:

Customers will have to pay for all return charges to our store (Local & International): Our team will inspect the item to ensure that it is in its original packing, unopened and unused. Refunds will then be issued accordingly.

Payments via debit/card: All payments made via a debit or a credit card will be refunded directly to your card.

Cash Payment:

All Payments made in Cash will be refunded immediately at the time the product is returned to our store and inspected by our staff.