Shopping cart
You have no items in your shopping cart.
You have no items in your shopping cart.
Supply voltages (please state when ordering) |
24 V, 50–60 Hz other voltage versions on request |
Power consumption (real power) | 230 V, 50–60 Hz version = 0,4–1,1 W 24 V AC / DC version = 0,2 – 1,1 W (depending on the switching status) |
Channel (potential-free) | Change-over, contact gap < 3 mm (μ) |
Control input | voltage and phase of power supply |
Contact material | AgNi + Au (hard gold plated contact) |
Switching capacity per channel resistive load: inductive load: |
16 A / 250 V~ at cosϕ=1 10 A at cosϕ=0,6 |
Min. switching power | 50 mW (5 V / 2 mA) |
Max. starting current | 30 A |
Functionality | 20 different functions |
Time range (free adjustable) |
000:00:00:1 up to 999:59:59:9 [hhh:mm:ss:1/10s] |
Minimum interval | 0,1 sec. |
Debouncing time / operating time | max. 64 msec. |
Reactivation time | max. 1,5 sec. |
Time base | Quartz |
Quartz accuracy (at 20°C) |
≤ ±0,5 sec./day (Quartz accuracy optimized for typical ambient conditions) |
Lifespan relay | 10 A = approx. 100,000 switchings |
Power back-up (at 20°C) | approx. 10 years (depends on the Lithium-battery life) |
Program security | unlimited (E2-Prom) |
Display | high resolution LCD 15 mm (visible area 7,5 mm2) |
Permitted ambient temperature | -30° … +55°C |
Housing | self-extinguishing thermoplastic |
Dimensions | 45 x 35 x 58 mm |
Mounting | 35 mm DIN-rail |
Type of connection | Screw terminals (pull-up type) |
Type of protection | IP 20 to DIN EN 60529 |
Class of protection | II when installed according to regulations |